Pump Sizing Calculator

Work out the duty point — the flow and head a pump must deliver — plus the motor it needs and, for boosters, the pressure tank that keeps it inside its start limit. Built on National Building Code water norms and the Hunter fixture-unit method.

1. What is the pump for?

2. How high?

m

About 3 m a floor, plus 2 m for the tank stand. G+8 ≈ 29 m.

m

Lowest water level in the sump. Use 0 if water sits above the pump.

3. How much water a day?

Daily water use

NBC assumes 5.

  • Flats / houses: 50 × 5 people × 135 L33,750 L

Total per day33,750 L (33.8 m³)

hours

We size for 4 hours by default, which leaves room to catch up after a power cut.

4. Pumps and pipework

Pumps working together at peak.

Spares that take over if one fails.

Pipe details
m

Vertical rise plus horizontal runs.

% extra

Added to straight-pipe friction.

Your pump

8.44 m³/h at 38.9 m head

141 L/min · 1 running + 1 standby

Motor per pump

2.2 kW (3 HP)

Shaft power 1.63 kW at 55% efficiency

Pipe

40 NB (1½")

1.70 m/s, sized for you

Electricity

7.65 kWh/day

4 h of running

Total flow

8.44 m³/h

141 L/min

Pump type that fits

Monoblock pump or openwell submersible

Where the head comes from

Lift (tank height + water depth)
32.0 m
Discharge at the tank inlet
2.00 m
Friction (50 m pipe + 25% fittings)
4.88 m
Total head
38.9 m
System curve and duty point
01020304050024681012Total flow (m³/h)Head (m)Lift + residual (34.0 m)Duty point: 8.44 m³/h @ 38.9 m

Pick a pump whose curve crosses this line at or just right of the duty point. Hover to read the head at any flow.

Indicative sizing for planning and budgeting. Final selection depends on the site and on the actual pump, resin or heat pump chosen — our engineers check every quote against it.

How this calculator sizes a pump

A pump is defined by its duty point: the flow it must deliver and the head it must deliver it against. Every other choice — the motor, the pipe, the pump type — follows from those two numbers.

Flow when filling a tank

For a transfer pump, the flow is the day’s water divided by the hours you are willing to run the pump:

Flow (m³/h) = daily water use (L) ÷ 1,000 ÷ run hours

We default to 4 hours. A pump sized to fill the tank in 4 hours can catch up after a power cut or a dry sump, and it isn’t so oversized that it hammers the pipework. You can change it.

If you don’t know the daily use, the calculator estimates it from the National Building Code of India (NBC 2016, Part 9) per-head norms:

BuildingNorm
Homes and flats135 L per person a day (150–200 L for premium homes), 5 people per flat
Offices45 L per person
Hotels180 L per bed (320 L for 4-star and above)
Hospitals340 L per bed (450 L above 100 beds)
Hostels and boarding schools135 L per resident
Day schools45 L per person
Restaurants70 L per seat
Factories45 L per worker (30 L without bathrooms)
Gardensabout 5 L per m² a day

Example: 50 flats × 5 people × 135 L = 33,750 L a day. Over 4 hours, that is 8.44 m³/h (141 L/min).

Flow when holding pressure

A booster pump has no tank to fill. It runs when taps open, so it must keep up with the busiest minute, not the average hour. The calculator gives you three ways to find that peak:

  1. Count fixtures. Each fixture carries a load in water supply fixture units (WSFU): a cistern WC is 2.2, a wash basin 0.7, a shower or kitchen sink 1.4, a flush-valve WC 10. Hunter’s curve converts the building’s total into a probable peak flow. Fifty flats with two bathrooms each add up to about 570 WSFU, or around 520 L/min.
  2. Count users. Daily use ÷ hours of heavy use × a peak factor (default 4 hours and 1.5×).
  3. Enter a measured flow from a flow meter, a data logger or the existing system.

Hunter’s method dates from the 1940s and runs high with today’s low-flow fittings. The calculator shows both estimates side by side, so you can see when they disagree.

Head: lift, friction and pressure

Total head = static lift + friction + pressure (or discharge) at the outlet

  • Static lift is the vertical distance from the lowest water level in the sump or borewell to the outlet. As a rule of thumb, allow about 3 m per floor plus 2 m for the tank stand.
  • Pressure at the outlet — 1 bar is 10.2 m of head. A tank inlet needs about 2 m just to discharge. A booster serving showers needs about 2 bar at the highest outlet, and a rain shower about 2.5 bar.
  • Friction uses the Hazen-Williams equation: h = 10.67 × L × Q^1.852 ÷ (C^1.852 × d^4.87), with Q in m³/s and d in metres. C is 140 for uPVC and CPVC and 120 for GI. Bends, valves and fittings add 25% by default.

The calculator picks the smallest standard pipe that keeps water at or under 1.8 m/s. Faster than about 2 m/s, pipes get noisy and friction climbs steeply.

From head to motor

Hydraulic power (kW) = 9.81 × flow (m³/s) × head (m)

Divide by pump efficiency — 55% is typical for small and mid-size centrifugal pumps — to get shaft power. Add 10% margin, then round up to the next standard motor: 0.37, 0.55, 0.75, 1.1, 1.5, 2.2, 3.0, 3.7 kW and so on.

Worked example

Fifty flats, an overhead tank 30 m above the pump, and the sump water level 2 m below it:

StepValue
Flow33,750 L ÷ 4 h = 8.44 m³/h
Static lift30 + 2 = 32 m
Discharge at tank2 m
Friction, 50 m of 40 NB at 1.7 m/s3.9 m + 25% = 4.9 m
Total head38.9 m
Hydraulic power9.81 × 0.00234 × 38.9 = 0.89 kW
Shaft power at 55%1.62 kW
Motor2.2 kW (3 HP)

Running and standby pumps

With more than one pump running, each one carries its share of the flow at the same head. Two running pumps on the example above would each be 4.2 m³/h at 38.9 m. Standby pumps don’t change the duty point — they’re identical spares. An automatic controller should alternate duty and standby, so both pumps wear evenly and the standby is proven to work when it’s needed.

Sizing the pressure tank

A fixed-speed booster switches on at the cut-in pressure and off at cut-out. Every motor start heats the winding, so each pump has a limit on starts per hour — commonly up to 60 for small surface pumps, fewer for larger motors and submersibles. The tank supplies water between cut-out and cut-in, so the pump doesn’t start for every glass of water.

Cycling is fastest when demand is exactly half the pump’s flow. One on/off cycle then takes 4 × drawdown ÷ pump flow, which sets the drawdown the tank must hold:

Drawdown (L) = pump flow (L/s) × (3,600 ÷ starts per hour) ÷ 4

Only part of a diaphragm tank is usable. With the air precharge set 0.2 bar below cut-in, Boyle’s law gives the usable fraction from absolute pressures:

Usable fraction = (P_off − P_on) ÷ P_off × P_pre ÷ P_on

Example: a 120 L/min pump limited to 60 starts an hour needs 2 L/s × 60 s ÷ 4 = 30 L of drawdown. On a 3.0 to 4.0 bar switch, about 19% of the tank is usable, so it needs 30 ÷ 0.19 = 158 L — a 200 L tank. Widening the band to 1.5 bar, or a pump that allows more starts, shrinks the tank. The calculator shows this trade-off as a table.

With several pumps in cascade, size the tank for one pump: the last pump to switch is the one that cycles. A variable-speed (VFD) booster slows down instead of switching off, so it needs only a small tank.

Questions people ask

How do I calculate the HP of a water pump for my building? +

Find the flow (daily water use divided by the hours the pump may run) and the total head (lift + friction + the pressure needed at the outlet). Hydraulic power in kW is 9.81 × flow in m³/s × head in metres. Divide by pump efficiency (about 0.55 for small pumps), add 10% margin, and round up to the next standard motor. For 50 flats lifting 30 m, that is a 2.2 kW (3 HP) motor.

How many hours a day should a water pump run? +

We size transfer pumps to fill a day’s water in about 4 hours. That leaves room to catch up after a power cut or a dry sump, without a pump so large that it hammers the pipes. Over 8 hours a day usually means the pump is too small.

What is total head? +

Total head is the energy the pump adds, written as metres of water. It is the vertical lift from the water surface to the outlet, plus friction in pipes and fittings, plus the pressure you want left at the outlet (1 bar ≈ 10.2 m).

Do I need a standby pump? +

For any building where a day without water is not acceptable — apartments, hotels, hospitals — yes. The standby is identical to the duty pump. An automatic controller alternates them, so both wear evenly and the standby is known to work.

What size pressure tank does a booster pump need? +

Size it so the pump never starts more often than its maker allows. Worst-case cycling happens when demand is half the pump’s flow; the drawdown needed is pump flow × (3600 ÷ starts per hour) ÷ 4. Divide by the tank’s usable fraction (set by the cut-in and cut-out pressures) to get the volume. A 120 L/min pump on a 3–4 bar switch limited to 60 starts an hour needs about a 200 L tank.

How many times can a pump start in an hour? +

Small surface pumps commonly allow up to around 60 starts an hour; larger motors and submersibles usually allow fewer. Use the figure in your pump’s manual. Fewer allowed starts means a bigger pressure tank or a wider pressure band.

What is a fixture unit? +

A water supply fixture unit (WSFU) is a weighting for how hard a fixture draws water and how often. A WC with a cistern counts 2.2, a wash basin 0.7, a shower 1.4. Add them up for the building, and Hunter’s curve converts the total into the probable peak flow — the flow a booster must meet.